EtherNet/IP standard I/O connection timeout

A Logix controller drops a standard EtherNet/IP I/O connection after RPI times a multiplier of at least 4, and never in less than 100 ms, while an OMRON NJ/NX controller defaults to 4 times the RPI with a floor of only 10 ms.

Vendor or body
ODVA (protocol); values as documented by Rockwell Automation and OMRON
Model or version
EtherNet/IP implicit (I/O) connections; Rockwell Automation Logix controllers; OMRON NJ/NX-series controllers (built-in EtherNet/IP port tag data links)
Last verified
Oct 5, 2026
Sourced values
13

Values

ParameterValueCondition
Connection timeoutMultiplier x RPI1Implicit (I/O) messages. The controller firmware selects the multiplier.
Minimum timeout multiplier41Logix controllers
Minimum connection timeout100 ms1Logix controllers. The firmware picks a multiplier large enough that the timeout is at least 100 ms.
Timeout at RPI 2 ms128 ms1Rockwell Automation example; controller multiplier 64
Timeout at RPI 10 ms160 ms1Rockwell Automation example; controller multiplier 16
Connection timeout, OMRON NJ/NX controllers4, 8, 16, 32, 64, 128, 256 or 512 x RPI2Tag data links on the NJ/NX built-in EtherNet/IP port. The default is 4 x RPI.
Minimum connection timeout, OMRON NJ/NX controllers10 ms2Connection settings in Sysmac Studio. At a 10 ms RPI and the default multiplier of 4, the connection times out after 40 ms, where the Logix example above waits 160 ms.
RPI range for I/O devicesDevice dependent3Valid ranges and defaults depend on the device; Logix Designer shows the valid range under the RPI field.
Where RPI limits are definedDevice EDS file4ODVA recommends that device makers define minimum, maximum, and default RPI with a ParamN entry in the EDS, so tools do not pick a value beyond the device capacity.
RPI range, standard produced and consumed tags0.196 to 536870.911 ms5ControlLogix controllers
RPI range, standard produced and consumed tags1 to 536870.911 ms5CompactLogix controllers
Meaning of RPIProducer send interval4Producers send data packets at the RPI, and consumers listen for a packet at the same interval.
Transport for cyclic I/OUDP6EtherNet/IP runs CIP over standard Ethernet and TCP/IP and uses UDP for real time cyclic data.

Sources

  1. EtherNet/IP Network Devices User Manual (ENET-UM006C-EN-P). Read Oct 5, 2026.
  2. NJ/NX-series CPU Unit Built-in EtherNet/IP Port User's Manual (W506-E1-37). Read Oct 5, 2026.
  3. Connection view parameters (Rockwell Automation add-on profile help). Read Oct 5, 2026.
  4. EtherNet/IP Quick Start for Vendors Handbook (PUB00213R0). Read Oct 5, 2026.
  5. Logix 5000 Controllers Produced and Consumed Tags (1756-PM011N-EN-P). Read Oct 5, 2026.
  6. EtherNet/IP (ODVA). Read Oct 5, 2026.

About this page

Built from 6 sources: 2 protocol owners and alliances and 4 vendor documents. Researched and drafted with AI assistance, then reviewed and approved by Ben Rutter on . How pages are made

First published
Last updated
Change history (1)
  • First published
Cite this page

Plain

Ben Rutter. "EtherNet/IP standard I/O connection timeout." OT Wireless, published October 5, 2026. https://otwireless.com/requirements/ethernet-ip-io/

APA 7

Rutter, B. (2026, October 5). EtherNet/IP standard I/O connection timeout. OT Wireless. https://otwireless.com/requirements/ethernet-ip-io/

BibTeX

@misc{rutter2026ethernetipio,
  author = {Rutter, Ben},
  title = {{EtherNet/IP standard I/O connection timeout}},
  year = {2026},
  howpublished = {\url{https://otwireless.com/requirements/ethernet-ip-io/}},
  organization = {OT Wireless},
}