PROFIsafe F-monitoring time (F_WD_Time)
A PROFIsafe connection goes to a safe state when the next valid safety message does not arrive within F_WD_Time, a monitoring time in milliseconds that you set for each F-device.
- Vendor or body
- PROFIBUS and PROFINET International (protocol); values as documented by Siemens
- Model or version
- PROFIsafe over PROFINET; Siemens SIMATIC Safety in TIA Portal
- Last verified
- Oct 5, 2026
- Sourced values
- 9
Values
| Parameter | Value | Condition |
|---|---|---|
| F_WD_Time | Watchdog in ms1 | An F-Parameter the F-Device receives at startup. It sets a watchdog timer, in milliseconds, that monitors the reception of the next valid PROFIsafe message (SPDU). |
| Reaction when communication fails | Safe state1 | PROFIsafe communication errors switch the F-Host driver into a safe state. A return to normal operation is usually not allowed without operator acknowledgment. |
| Where it is set (Siemens) | CPU, interface, or F-I/O2 | Siemens calls F_WD_Time the F-monitoring time. You set a default for central F-I/O in the F-CPU properties, a default per PROFINET or PROFIBUS interface, or an individual value in each F-I/O. Changing it changes the safety program, so a new acceptance may be required. |
| Default for GSD based F-devices | From the GSD file2 | For fail-safe GSD based I/O devices, the F-monitoring time in the device GSD file becomes the default when the device is plugged in. You can change it. |
| F-monitoring time range | 1 to 65535 ms3 | Example module ET 200MP F-DI 16x24VDC (6ES7526-1BH00-0AB0). Ranges are module specific. |
| Default F-monitoring time, S7-1500HF systems | 2300 ms2 | Default for F-I/O in a redundant HF system, sized for an MRP ring. Siemens says a line topology can use a value smaller by a factor of about 2. |
| Minimum F-monitoring time | Calculated per system2 | Siemens: the PROFIsafe monitoring time must be long enough that it does not trip when no fault is present. Siemens provides an Excel file (entry 109783831) to calculate the minimum. |
| Role in safety function response time | Adds a delta1 | PI: the safety function response time is the total worst case delay time plus, for one failed part, the difference between its watchdog time and its worst case delay time. |
| Wireless transmission | Permitted1 | PI permits wireless transmission as long as sufficient availability (no nuisance trips) and security can be guaranteed. For IEEE 802.11, only infrastructure mode is permitted, not ad hoc mode. |
Sources
- PROFIsafe System Description, Technology and Application (Order No. 4.342). Read Oct 5, 2026.
- SIMATIC Safety, Configuring and Programming, Programming and Operating Manual (A5E02714440-AR). Read Oct 5, 2026.
- Digital input module F-DI 16x24VDC (6ES7526-1BH00-0AB0) Manual (A5E03858068-AA). Read Oct 5, 2026.
About this page
Built from 3 sources: 1 protocol owner or alliance and 2 vendor documents. Researched and drafted with AI assistance, then reviewed and approved by Ben Rutter on . How pages are made
- First published
- Last updated
Change history (1)
- First published
Cite this page
Plain
Ben Rutter. "PROFIsafe F-monitoring time (F_WD_Time)." OT Wireless, published October 5, 2026. https://otwireless.com/requirements/profisafe/
APA 7
Rutter, B. (2026, October 5). PROFIsafe F-monitoring time (F_WD_Time). OT Wireless. https://otwireless.com/requirements/profisafe/
BibTeX
@misc{rutter2026profisafe,
author = {Rutter, Ben},
title = {{PROFIsafe F-monitoring time (F\_WD\_Time)}},
year = {2026},
howpublished = {\url{https://otwireless.com/requirements/profisafe/}},
organization = {OT Wireless},
}